1. General Introduction
ADV151 Digital Input Module can be installed on Field Control Unit or ESB bus node unit for 24VDC Voltage Input digital signals from field instrument. Three types of connection selectable as Pressure clamp terminal, MIL connector cable or dedicated cable AKB331, Dual-redundant communication is available by installing two communication modules on the same unit.
2. Standard Specification
Main Characters | Description |
Number of input channels | 32, isolated |
Rated input voltage | 24 V DC (sink/source) |
Input ON voltage | 18 to 26.4 V DC |
Input OFF voltage | 5.0 V DC or less |
Input current (at rated input voltage | 4.1 mA±20 % / channel |
Maximum allowable input voltage | 30.0 V DC |
Withstanding voltage | Between input signal and system: 2 kV AC, For 1 minute Between commons: 500 V AC, For 1 minute, common every 16-channel |
Input response time | 8 ms or less (for status input) |
Minimum ON detection time | 20 ms (for pushbutton input) |
Maximum ON/OFF cycle | 25 Hz (for pushbutton input) |
Maximum current consumption | 500 mA (5 V DC) |
External connection | Pressure clamp terminal, MIL connector cable, dedicated cable (AKB331) |
3. Model Selection of ADV151 Digital Input Module
Model | Suffix Codes | Description | |||
ADV151 | Digital Input Module (32-channel, 24 V DC, Isolated) | ||||
-P | With pushbutton input | ||||
-E | With SOE capture | ||||
5 | Without status display; with no explosion protection | ||||
6 | With status display; with no explosion protection | ||||
E | Without status display; with explosion protection | ||||
F | With status display; with explosion protection | ||||
0 | Basic type | ||||
3 | With ISA Standard G3 option and temperature (-20 to 70 °C) option | ||||
Option Code | /D5A00 | With KS Cable Interface Adapter for 32-channel digital [Model: ATD5A-00] | |||
/B5S00 | With Pressure Clamp Terminal Block for Digital Input [Model: ATB5S-00] | ||||
/B5S10 | With Pressure Clamp Terminal Block for Digital Input (surge absorber) [Model: ATB5S-10] | ||||
/B5D00 | With Dual Pressure Clamp Terminal Block for Digital Input [Model: ATB5D-00] | ||||
/B5D10 | With Dual Pressure Clamp Terminal Block for Digital Input (surge absorber) [Model: ATB5D-10] | ||||
/CCC01 | With Connector Cover for MIL Cable [Model: ACCC01] |
4. Typical Order Codes
Typical order codes | Remarks |
ADV151-P50 | Standard type |
ADV151-P60 | Standard type with status display |
ADV151-P53 | Standard type, G3 option and wide temperature (-20 to 70 °C) option |
ADV151-P63 | Standard type with status display, G3 option and wide temperature (-20 to 70 °C) option |
ADV151-P50/D5A00 | Standard type with ATD5A terminal block |
ADV151-P60/D5A00 | Standard type with status display, with ATD5A terminal block |
ADV151-P53/D5A00 | Standard type, G3 option and wide temperature (-20 to 70 °C) option, with ATD5A terminal block |
ADV151-P63/D5A00 | Standard type with status display, G3 option and wide temperature (-20 to 70 °C) option, with ATD5A terminal block |
5.External Dimension
Address: P.O. Box 17033, Jebel Ali Free Zone - South 2 Dubai, United Arab Emirates
Tel: +971558915937
Fax: +971558915956
E-mail:
info@rostockgroup.com
technical@rostockgroup.com
commercial@rostockgroup.com
Get the latest special offers and discount information sent to your email address.
Copyright © Rostock Group Co.,Limited All Rights Reserved. Sitemap