1. General information
Bartec HSB heating tape is suitable for frost protecting in industrial areas. The level of its maximum possible heating output allows the heating tape to be used for maintaining high process temperatures. It's a parallel heating tape with steam cleaning possible and self-limiting which can be used in explosive atmospheres without temperature limiter (subject to ‘T’ class) and cut to length at random thanks to its parallel circuit configuration HSB’s simple installation thanks favorable dimensions. Easy on-site cutting and terminating, even in Ex areas Corrosion-proof and resistant to chemical attack thanks to its protective outer jacket.
A temperature-dependant resistive element between two parallel copper conductors regulates and limits the power output of the heating tape. This output regulation is carried out automatically along the entire length of the heating tape according to the prevailing ambient temperature. If the ambient temperature rises, the power output of the tape is reduced. This self-limiting property prevents overheating even when the tapes are crossed.
Thanks to the parallel design the heating tape can be cut to any required length. This feature considerably simplifies project planning and installation. The heating tape is cut and terminated directly on the construction site according to the circumstances. The heating system must be designed to ensure that the maximum operating temperature of +120 °C will not be exceeded when it is energized. When switched off, heating tape can be exposed to a temperature of 200 °C for a short time, not more than 1,000 hours cumulated.
2. Specification of HSB heating tape
Technical data | |
Nominal voltage | AC 208 V to 254 V, AC 110 V to 120 V |
Max. exposure temperature | power on: +120 °C |
Max. withstand temperature | power off +200 °C |
Min. installation temperature | -60 °C |
Min. start-up temperature | -60 °C |
Max. braid resistance | <18.2 Ω/km |
Dimensions with braiding and jacket | 10.2 mm x 4.8 mm with fluoropolymer protective jacket |
Min. bending radius | 25 mm |
Explosion protection | |
Marking | II 2G Ex e IIC 200 °C (T2), T3, T4 Gb II 2D Ex tb IIIC T200 °C, T195 °C, T130 °C Db |
Certification System | KEMA 08 ATEX 0111 X IECEx KEM 09.0084X TC RU C-DE.ГБ06.B.00230 CSA 1862457 |
Certification Heating tape | KEMA 02 ATEX 2327 U IECEx KEM 07.0048 U DNV E-12874 |
3. Selection of HSB
Power setting at +10 °C | |||||||||||||
Power output | HSB10 | HSB15 | HSB25 | HSB30 | HSB45 | HSB60 | |||||||
at AC 230V | 10W/m | 15W/m | 25W/m | 30 W/m | 45 W/m | 60 W/m | |||||||
at AC 120V | 10W/m | 15W/m | 25W/m | 30 W/m | 45 W/m | 60 W/m | |||||||
Max. length of heating circuit at AC 230 V for automatic circuit-breakers with C characteristic | |||||||||||||
Circuit breaker size | start-up temperature | HSB10 | HSB15 | HSB25 | HSB30 | HSB45 | HSB60 | ||||||
16A | +10 °C | 200 m | 165m | 120m | 85m | 70m | 50m | ||||||
-25 °C | 175 m | 117 m | 88m | 69m | 49m | 38m | |||||||
-60°C | 165 m | 110m | 80m | 65m | 45m | 39m | |||||||
20A | +10 °C | 235 m | 189 m | 140 m | 114m | 82m | 64m | ||||||
-25 °C | 235m | 152 m | 120m | 92m | 66m | 52m | |||||||
-60°C | 225 m | 144m | 114 m | 86m | 62 m | 48m | |||||||
25A | +10 °C | 235m | 189 m | 140 m | 114m | 82m | 64m | ||||||
-25 °C | 235m | 170 m | 130m | 100m | 75 m | 58m | |||||||
-60°C | 230 m | 160m | 120m | 92m | 70m | 52m | |||||||
32A | +10 °C | 235m | 189 m | 140 m | 114m | 82m | 64m | ||||||
-25 °C | 235m | 189 m | 140 m | 114m | 82m | 64m | |||||||
-60°C | 235m | 189 m | 136m | 110m | 78m | 60m | |||||||
Max. length of heating circuit at AC 120 V for automatic circuit-breakers with C characteristic | |||||||||||||
Circuit breaker size | start-up temperature | HSB10 | HSB15 | HSB25 | HSB30 | HSB45 | HSB60 | ||||||
16A | +10 °C | 100 m | 80 m | 60m | 44m | 35m | 25m | ||||||
-25 °C | 89 m | 56m | 44m | 35m | 24m | 20m | |||||||
-60°C | 82 m | 52 m | 40m | 32m | 22m | 17m | |||||||
20A | +10 °C | 120m | 95 m | 69 m | 58m | 41 m | 32 m | ||||||
-25 °C | 120m | 75 m | 59 m | 45 m | 33m | 25 m | |||||||
-60°C | 120m | 75 m | 55m | 41m | 26m | 21m | |||||||
25A | +10 °C | 120m | 95 m | 69 m | 58m | 41 m | 32 m | ||||||
-25 °C | 120m | 80m | 64 m | 50m | 35 m | 28m | |||||||
-60°C | 120m | 80m | 60m | 45 m | 32m | 26m | |||||||
32A | +10 °C | 120m | 95 m | 69 m | 58m | 41 m | 32 m | ||||||
-25 °C | 120m | 95 m | 69 m | 58m | 41 m | 32 m | |||||||
-60°C | 120m | 95 m | 69 m | 58m | 41 m | 32 m |
Address: P.O. Box 17033, Jebel Ali Free Zone - South 2 Dubai, United Arab Emirates
Tel: +971558915937
Fax: +971558915956
E-mail:
info@rostockgroup.com
technical@rostockgroup.com
commercial@rostockgroup.com
Get the latest special offers and discount information sent to your email address.