1. General Information
Bartec MSB heating tape is suitable for electric trace heating in the industrial area and can be exposed to a temperature of up to 130 °C (power off), with the halogen-free protective jacket, the heating tape is resistant to oil, greases and most chemicals.MSB can be used in temperature class T4 in Ex area and cut to length at random thanks to its parallel circuit configuration The simple installation thanks to its high flexibility and favorable dimensions. A temperature-dependant resistive element between two parallel copper conductors regulates and limits the heat output of the heating tape. This output regulation is carried out automatically along the entire length of the heating tape according to the prevailing ambient temperature. If the ambient temperature rises, the power output of the tape is reduced. Thanks to the parallel design the heating tape can be cut to any required length. This feature considerably simplifies project planning and installation. The heating tape is cut and terminated directly on the construction site according to the circumstances. If the tape will be damaged, it is not necessary to replace the whole tape.
2. Specification of MSB heating tape
Technical data | |
Nominal voltage | AC 208 V to 254 V |
Max. exposure temperature | power on +110 °C |
Max. withstand temperature | power off +130 °C |
Min. installation temperature | -40 °C |
Min. start-up temperature | -50 °C |
Max. braid resistance | <18.2 Ω/km |
Dimensions with braiding and jacket | 10.2 mm x 4.8 mm with TPC jacket |
Min. bending radius | 25 mm |
Explosion protection | |
Marking | II 2G Ex e IIC T150 °C (T3), T4 Gb II 2D Ex tb IIIC T150 °C, T130 °C Db |
Certification System | KEMA 08 ATEX 0110 X IECEx KEM 09.0083X |
Certification Heating tape | DEKRA 12 ATEX 0044 U IECEx DEK 12.0004 U DNV E-12874 |
3. Selection of MSB
Power setting at +10 °C | ||||||
Power output | MSB10 | MSB15 | MSB25 | MSB30 | MSB40 | |
at AC 230V | 10W/m | 15W/m | 25W/m | 30W/m | 40W/m | |
Max. length of heating circuit at AC 230 V for automatic circuit-breakers with C characteristic | ||||||
Circuit breaker size | start-up temperature | MSB10 | MSB15 | MSB25 | MSB30 | MSB40 |
16A | +10 °C | 200 m | 165m | 120m | 85m | 70m |
-25 °C | 175 m | 117 m | 88m | 69m | 49m | |
-50°C | 165 m | 110m | 80m | 65m | 45m | |
20A | +10 °C | 235 m | 189 m | 140 m | 114 m | 82 m |
-25°C | 235 m | 152m | 120m | 92m | 66m | |
-50°C | 225m | 144 m | 114m | 86m | 62m | |
32A | +10 °C | 235 m | 189 m | 140 m | 114 m | 82 m |
-25 °C | 235 m | 189 m | 140 m | 114 m | 82 m | |
-50°C | 235 m | 189 m | 136m | 110m | 78m | |
Permissible ambient temperature for T class | ||||||
Nominal voltage | Heating cable | max. work piece temperature | T class | |||
at AC 230V | all | +110 °C | 150 °C (T3) | |||
MSB10 | +100 °C | T4 | ||||
MSB15 | +90 °C | T4 | ||||
MSB25 | +80℃ | T4 | ||||
MSB30 | +70℃ | T4 | ||||
MSB40 | +60℃ | T4 |
Address: P.O. Box 17033, Jebel Ali Free Zone - South 2 Dubai, United Arab Emirates
Tel: +971558915937
Fax: +971558915956
E-mail:
info@rostockgroup.com
technical@rostockgroup.com
commercial@rostockgroup.com
Get the latest special offers and discount information sent to your email address.