1. General Information
Bartec PSBL heating tape is for electric trace heating for frost protection of pipelines and vessels in explosive atmosphere, two parallel positioned copper wires with a cross-section of 1 mm² an irradiated electrically conducting polymer is extruded, can be used in explosive atmospheres without temperature limiter and cut to any length due to the parallel current supply. Resistant to corrosion and chemical influences because of the external protective jacket. PSBL use Tinned copper braiding for electrical and mechanical protection which is easy installation due to high level of flexibility. Electrically conducting matrix responds to changes of the ambient temperature with an increase or decrease of the heating output. A flame-retardant, UV-resistant jacket protects the braiding against humidity and offers additional protection against mechanical stress. The heating system must be designed to ensure that the maximum operating temperature of 65 °C will not be exceeded when it is energized. When it is switched off, the heating tape can be exposed to a temperature of 85 °C, not more than 1,000 hours cumulated.
2. Specification of PSBL heating tape
Technical data | |
Nominal voltage | AC 208 V to 254 V, AC 110 V to 120 V |
Max. exposure temperature | power on +65 °C |
Max. withstand temperature | power off +85 °C |
Min. installation temperature | -55 °C |
Min. start-up temperature | -30 °C |
Max. braid resistance | < 18.2 Ω/km |
Dimensions with braiding and jacket | 10.5 x 6.0 mm with polyolefin protective jacket 10.3 x 5.8 mm with fluoropolymer protective jacket |
Min. bending radius | 25 mm |
Explosion protection | |
Marking | II 2G Ex e IIC T5 Gb II 2D Ex tb IIIC T95 °C Db |
Certification System | KEMA 08 ATEX 0112 X IECEx KEM 09.0085X TC RU C-DE.ГБ06.B.00230 |
Certification Heating tape | KEMA 02 ATEX 2326 U IECEx KEM 07.0047 U DNV E-12874 |
3. Selection table of PSBL
Power setting at +10 °C | ||||||
Power output | PSBL10 | PSBL15 | PSBL20 | PSBL25 | PSBL30 | |
at AC 230V | 10W/m | 15W/m | 20W/m | 25W/m | 30W/m | |
at AC 120V | 10W/m | 15W/m | 20W/m | 25W/m | 30W/m | |
Max. length of heating circuit at AC 230 V for automatic circuit-breakers with C characteristic | ||||||
Circuit breaker size | start-up temperature | PSBL10 | PSBL15 | PSBL20 | PSBL25 | PSBL30 |
10A | +10 °C | 118 m | 104m | 79m | 60m | 45m |
-15 °C | 90 m | 69 m | 49m | 39m | 24m | |
-30°C | 77 m | 56m | 40m | 30m | 16m | |
16A | +10 °C | 154 m | 139m | 110m | 83m | |
-15°C | 136 m | 89m | 71m | 56m | ||
-30°C | 118 m | 78m | 58m | 47m | ||
Max. length of heating circuit at AC 120 V for automatic circuit-breakers with C characteristic | ||||||
Circuit breaker size | start-up temperature | PSBL10 | PSBL15 | PSBL20 | PSBL25 | |
10A | +10 °C | 49 m | 43 m | 33m | 25m | |
-15 °C | 45 m | 35 m | 25m | 20m | ||
-30°C | 39 m | 28 m | 20m | 15m | ||
16A | +10 °C | 77 m | 58m | 46m | 35m | |
-15°C | 68 m | 45m | 36m | 28m | ||
-30°C | 59 m | 39m | 29m | 24m |
Address: P.O. Box 17033, Jebel Ali Free Zone - South 2 Dubai, United Arab Emirates
Tel: +971558915937
Fax: +971558915956
E-mail:
info@rostockgroup.com
technical@rostockgroup.com
commercial@rostockgroup.com
Get the latest special offers and discount information sent to your email address.
Copyright © Rostock Group Co.,Limited All Rights Reserved. Sitemap