1. General Introduction
It transfers the analog input signal to the safe area as two isolated current values. Digital signals may be superimposed on the input signal in the hazardous or safe area and are transferred bi-directionally. If the HART communication resistance in the loop is too low, the internal resistance of 250 between terminals 8, 9 and 11, 12 can be used. Test sockets for the connection of HART communicators are integrated into the terminals of the device.
2. General Specification for KFD2-STC4-EX1.2O
Model | KFD2-STC4-EX1.2O |
General specifications | |
Signal type | Analog input |
Functional safety related parameters | |
Safety Integrity Level (SIL) | SIL 3 |
Supply | |
Connection | Power Rail or terminals 14+, 15- |
Rated voltage Ur | 20 ... 35 V DC |
Ripple | within the supply tolerance |
Power dissipation | 1.8 W |
Power consumption | 2.4 W |
Input | |
Connection side | field side |
Connection | terminals 1+, 2-, 3 or 5-, 6+ |
Open circuit voltage/short-circuit current | terminals 1+, 3-: 22.7 V / 38 mA |
Voltage drop | terminals 5, 6 : ≤2.4 V at 20 mA |
Input resistance | terminals 2-, 3: ≤76 terminals 1+, 3: ≤500 (250 load) |
Available voltage | terminals 1+, 3: ≥16 V at 20 mA |
Output | |
Connection side | control side |
Connectio | terminals 7-, 8+,9; 10-, 11+,12 |
Connection | terminals 7-, 8+,9; 10-, 11+,12 |
Load | 0 ... 550 at 20 mA |
Output signal | 0/4 ... 20 mA (overload > 25 mA) |
Ripple | ≤50 A eff |
Transfer characteristics | |
Deviation | at 20 °C (68 °F), 0/4 ... 20 mA ≤± 10 A incl. calibration, linearity, hysteresis, loads and supply voltage |
Influence of ambient temperature | 0.25 μA/K |
Frequency range | field side into the control side: bandwidth with 0.5 Vpp signal 0 ... 7.5 kHz (-3 dB) control side into the field side: bandwidth with 0.5 Vpp signal 0.3 ... 7.5 kHz (-3 dB) |
Settling time | 200 μs |
Indicators/settings | |
Display elements | LED |
Labeling | space for labeling at the front |
Directive conformity | |
Electromagnetic compatibility | |
Directive 2014/30/EU | EN 61326-1:2013 (industrial locations |
Conformity | |
Electromagnetic compatibility | NE 21:2011 |
Degree of protection | IEC 60529:2001 |
Protection against electrical shock | UL 61010-1:2012 |
Ambient conditions | |
Ambient temperature | -20 ... 60 °C (-4 ... 140 °F) |
3. Connection
4. Assembly
Address: P.O. Box 17033, Jebel Ali Free Zone - South 2 Dubai, United Arab Emirates
Tel: +971558915937
Fax: +971558915956
E-mail:
info@rostockgroup.com
technical@rostockgroup.com
commercial@rostockgroup.com
Get the latest special offers and discount information sent to your email address.
Copyright © Rostock Group Co.,Limited All Rights Reserved. Sitemap