1. General Introduction
Pepperl+Fuchs HiCTB08-YRS-RRB-AK-CC-DI16 terminal board is 8 channel type for Yokogawa SIS Prosafe RS digital input module SDV144 which recommended to work with dual channel barrier HiC2832R1, as well as the connector pin assignment exactly fit the requirement of Yokogawa systems. Audible alarms, Information about missing supply voltage of the interface modules is available for the system as potential-free contact. The Termination Boards are supplied with a robust glass fiber reinforced plastic housing as standard. This design permits the fast and reliable installation on 35 mm DIN mounting rail acc. to EN 60715 in the cabinet.
2. Features
• System Board for Yokogawa ProSafe-RS
• For 16-channel DI card SDV144
• For 8 modules
• Recommended module: HiC2832R1 (DI)
• 24 V DC supply
• Hazardous area: spring terminals, blue
• Safe area: Yokogawa system connector, 50-pin
3. General Specification for HiCTB08-YRS-RRB-AK-CC-DI16
Technical data | HiCTB08-YRS-RRB-AK-CC-DI16 |
Supply | |
Rated voltage | 24 V DC, in consideration of rated voltage of used isolated barriers |
Voltage drop | 0.9 V, voltage drop across the series diode on the Termination Board must be considered |
Power loss | ≤ 600 mW |
Fusing | 2 A, in each case for 8 modules |
Reverse polarity protection | yes |
Electrical specifications | |
volt-free fault indication output | max. 30 V AC/40 V DC, 2 A |
Redundancy | |
Supply | Redundancy available. The supply for the modules is decoupled, monitored and fused. |
Indicators/settings | |
Display elements | LEDs PWR ON (Termination Board power supply) - LED power supply I, green LED - LED power supply II, green LED LED Fault (fault indication), red LED - LED flashes: power supply failure |
Directive conformity | |
Electromagnetic compatibility | |
Directive 2004/108/EC | EN 61326-1:2006 |
Conformity | |
Electromagnetic compatibility | NE 21:2011 For further information see system description. |
Protection degree | IEC 60529:2001 |
Ambient conditions | |
Ambient temperature | -20 ... 60 °C (-4 ... 140 °F) |
Storage temperature | -40 ... 70 °C (-40 ... 158 °F) |
Mechanical specifications | |
Protection degree | IP20 |
Connection | hazardous area connection (field side): spring terminals, blue safe area connection (control side): Yokogawa system connector, 50-pin |
Core cross-section | spring terminals: rigid: 0.2 ... 2.5 mm2 flexible: 0.25 ... 1.5 mm |
Material | housing: polycarbonate, 30 % fiberglass reinforced |
Mass | approx. 490 g |
Dimensions | 205 x 175 x 153 mm (8.1 x 6.9 x 6.02 in) |
Mounting | on 35 mm DIN mounting rail acc. to EN 60715:2001 |
Data for application in connection with Ex-areas | |
EC-Type Examination Certificate | CESI 10 ATEX 046 |
Safe area | |
Maximum safe voltage | 250 V (Attention! Um is no rated voltage.) |
Electrical isolation | |
Field circuit/control circuit | safe electrical isolation acc. to IEC/EN 60079-11, voltage peak value 375 V |
Directive conformity | |
Directive 94/9/EC | EN 60079-0:2012, EN 60079-11:2012, EN 60079-26:2007, EN 50303:2000 |
IECEx approval | IECEx CES 06.0003 |
Approved for | [Ex ia Ga] IIC [Ex ia Da] IIIC [Ex ia Ma] I |
Accessories | |
Designation | optional accessories: Label Carrier HiALC-Hi*TB-SET-1** |
4. Selection table
Termination Board & Barrier Module Selection table for Yokogawa Prosafe SIS system | ||||||
Yokogawa | Pepperl+Fuchs Termination Board | Pepperl+Fuchs Barrier Module | ||||
Prosafe | Channel | Class | Number of module | Type | Channel | Type |
Selection of Digital Input signals | ||||||
SDV144 | 16 | IS | 8 | HiCTB08-YRS-RRB-AK-CC-DI16 | 2 | HiC2832R1 |
SDV144 | 16 | IS | 16 | HiCTB16-YRS-RRB-AK-CC-DI16 | 1 | HiC2831R1 |
Selection of Digital Output signals | ||||||
SDV531 | 8 | IS | 8 | HiCTB08-YRS-RRB-AK-CC-DO08 | 1 | HiC2871 |
SDV541 | 16 | IS | 8 | HiCTB08-YRS-RRB-AK-CC-DO16 | 2 | HiD2872 HiD2876 |
SDV541 | 16 | IS | 16 | HiCTB08-YRS-RRB-AK-CC-DO16 | 1 | HiC2871 HiC2873 HiC2877 |
Selection of Analog Input signals | ||||||
SAl143 | 16 | IS | 16 | HiCTB16-YRS-RRB-KS-CC-AI16 | 1 | HiC2025 |
SAV144 | 16 | IS | 16 | HiCTB16-YRS-RRB-KS-CC-AI16-Y1 | 1 | HiC2025 |
SAl143 | 16 | IS | 8 | HiDTB08-YRS-RRB-KS-CC-Al16 | 2 | HiD2026 HiC2030 |
SAV144 | 16 | IS | 8 | HiDTB08-YRS-RRB-KS-CC-Al16-Y1 | 2 | HiD2026 HiC2030 |
Selection of Analog Output signals | ||||||
SAI533 | 8 | IS | 8 | HiCTB08-YRS-RRB-KS-CC-AO08 | 1 | HiC2031 |
5. Diagrams
Address: P.O. Box 17033, Jebel Ali Free Zone - South 2 Dubai, United Arab Emirates
Tel: +971558915937
Fax: +971558915956
E-mail:
info@rostockgroup.com
technical@rostockgroup.com
commercial@rostockgroup.com
Get the latest special offers and discount information sent to your email address.
Copyright © Rostock Group Co.,Limited All Rights Reserved. Sitemap