SDV531 Digital Output Module can be installed on Field Control Unit or Safety node unit for 24VDC Voltage digital on/off status signals field equipment. The output modules can be made dual-redundant respectively. They incorporate field wiring diagnostic functions, so they require no wiring diagnosis elements.
2. Standard Specification
Main Characters | Description |
Number of input channels | 8, isolated |
Output voltage | 24 V DC |
External power supply rating | 24 V DC, 5 A minimum |
External power supply | 24 V DC +20 %/–10 % , Current capacity: 5 A |
Maximum leak current at output off status | 1.6 mA |
Output format | Current source |
Maximum load current | 0.6 A/output line (4.8 A in total output lines) |
Output response time | 30 ms maximum |
Withstand voltage | 2 kV AC between output signal lines and system for 1 minute, 8-point input lines collectively connected (negative lines) |
Current consumption | 280 mA maximum (5 V DC), 140 mA maximum (24 V DC) |
External connection | Pressure clamp terminal, MIL cable, Dedicated signal cable AKB331 |
3. Model Selection
Model | Suffix Codes | Description | |||
SDV531 | Digital output module (8-channel, 24 V DC, module isolation) | ||||
-L | Long distance type | ||||
-S | Standard type | ||||
5 | For pressure clamp terminal block or MIL cable with no explosion protection | ||||
6 | With signal cable interface adapter and no explosion protection | ||||
E | For pressure clamp terminal block or MIL cable with explosion protection | ||||
F | With signal cable interface adapter and explosion protection | ||||
3 | With ISA Standard G3 and temperature (-20 to 70 °C) | ||||
C | With ISA Standard G3 and high-density installation (-20 to 70 ºC) | ||||
Option Code | /B4S00 | With pressure clamp terminal block for digital input (without surge absorber) [Model: STB4S-00] | |||
/B4S10 | With pressure clamp terminal block for digital input (with surge absorber) [Model: STB4S-10] | ||||
/B4D00 | With dual-redundant pressure clamp terminal block for digital input (without surge absorber) [Model: STB4D-00] | ||||
/B4D10 | With dual-redundant pressure clamp terminal block for digital input (with surge absorber) [Model: STB4D-10] | ||||
/PRP | With prevention pin of false insertion | ||||
/CCC01 | With connector cover for MIL cable (for flat ribbon cable) [Model: SCCC01] | ||||
/CCC02 | With connector cover for MIL cable (for discrete wire) [Model: SCCC02] |
4. Typical Order Codes
Typical order codes | Remarks |
SDV531-S53 | With pressure clamp terminal block |
SDV531-S63 | With KS interface adaptor |
5.External Dimension
Address: P.O. Box 17033, Jebel Ali Free Zone - South 2 Dubai, United Arab Emirates
Tel: +971558915937
Fax: +971558915956
E-mail:
info@rostockgroup.com
technical@rostockgroup.com
commercial@rostockgroup.com
Get the latest special offers and discount information sent to your email address.
Copyright © Rostock Group Co.,Limited All Rights Reserved. Sitemap