1. General Introduction
The AO801 Analog Output Module has 8 unipolar analog output channels. The module performs self diagnostic cyclically. A low internal power supply sets the module in INIT state (no signal from the module).
2. Specification of AO801
General info | |
Type | Analog Output |
Signal specification | 0... 20 mA, 4...20 mA |
Article number | 3BSE020514R1 |
Number of channels | 8 |
Signal type | Unipolar single ended |
HART | No |
SOE | No |
Redundancy | No |
High Integrity | No |
Intrinsic safety | No |
Mechanics | S800L |
Detailed data | |
Resolution | 12 bits |
Isolation | GroupWise isolated from ground |
Under/over range | - / +15% |
Output load | Max 850 Ω |
Error | 0.1% |
Temperature drift | Typ 30 ppm/°C, Max 50 ppm/°C |
Rise Time | 10 μs |
Update cycle time | 1 ms |
Current limiting | Built in current limited transmitter power |
Maximum field cable length | 600 meters (656 yards) |
Rated insulation voltage | 50 V |
Dielectric test voltage | 500 V a.c. |
Power dissipation | 3.8 W |
Current consumption +5 V Module bus | 70mA |
Current consumption +24 V Modulebus | - |
Current consumption +24 V external | 200 mA |
Supported wire size | Solid: 0.05-2.5 mm2, 30-12 AWG Stranded: 0.05-1.5 mm2, 30-12 AWG Recommended torque: 0.5-0.6 Nm Stripping length 6-7.5mm, 0.24-0.30 inch |
Diagnostics | |
Front LED’s | S(tatus) (run or fault) |
Status indication of supervision | Module Error, Module Warning, Channel error |
Environmental and certification | |
CE mark | Yes |
Electrical safety | IEC 61131-2, UL 508 |
Hazardous location | C1 Div 2 cULus, C1 Zone 2 cULus, ATEX Zone 2 |
Marine certification | ABS,BV,DNV-GL,LR,RS,CCS |
Protection rating | IP20 according to IEC 60529 |
Corrosive atmosphere ISA-S71.04 | G3 |
Climatic operating conditions | 0 to +55 °C (Storage -25 to +70 °C), RH=5 to 95 % no condensation, IEC/EN61131-2 |
Pollution degree | Degree 2, IEC 60664-1 |
Mechanical operating conditions | IEC/EN 61131-2 |
EMC | EN 61000-6-4 and EN 61000-6-2 |
Overvoltage categories | IEC/EN 60664-1, EN 50178 |
Equipment class | Class I according to IEC 61140; (earth protected) |
Max ambient temperature | 55 °C (131 °F), for vertical mounting 40 °C (104 °F) |
RoHS compliance | DIRECTIVE/2011/65/EU (EN 50581:2012) |
WEEE compliance | DIRECTIVE/2012/19/EU |
Dimensions | |
Width | 86.1 mm (3.4”) |
Depth | 58.5 mm (2.3”) |
Height | 110 mm (4.33”) |
Weight | 0.24 kg (0.53 lbs.) |
3. Selection table of I/O Modules
Name | HART | High Integrity | Intrinsic safety | Mechanics | Redundancy | SOE | Type |
AI801 | No | No | No | S800L | No | No | Analog Input |
AI810 | No | No | No | S800 | No | No | Analog Input |
AI815 | Yes | No | No | S800 | No | No | Analog Input |
AI820 | No | No | No | S800 | No | No | Analog Input |
AI825 | No | No | No | S800 | No | No | Analog Input |
AI830A | No | No | No | S800 | No | No | Analog Input |
AI835A | No | No | No | S800 | No | No | Analog Input |
AI843 | No | No | No | S800 | Yes | No | Analog Input |
AI845 | Yes | No | No | S800 | Yes | No | Analog Input |
AI880A | Yes | Yes | No | S800 | Yes | No | Analog Input |
AI890 | No | No | Yes | S800 | No | No | Analog Input |
AI893 | No | No | Yes | S800 | No | No | Analog Input |
AI895 | Yes | No | Yes | S800 | No | No | Analog Input |
AO801 | No | No | No | S800L | No | No | Analog Output |
AO810V2 | No | No | No | S800 | No | No | Analog Output |
AO815 | Yes | No | No | S800 | No | No | Analog Output |
AO820 | No | No | No | S800 | No | No | Analog Output |
AO845A | Yes | No | No | S800 | Yes | No | Analog Output |
AO890 | No | No | Yes | S800 | No | No | Analog Output |
AO895 | Yes | No | Yes | S800 | No | No | Analog Output |
Address: P.O. Box 17033, Jebel Ali Free Zone - South 2 Dubai, United Arab Emirates
Tel: +971558915937
Fax: +971558915956
E-mail:
info@rostockgroup.com
technical@rostockgroup.com
commercial@rostockgroup.com
Get the latest special offers and discount information sent to your email address.
Copyright © Rostock Group Co.,Limited All Rights Reserved. Sitemap